The function of the air cooler is to cool or condense. It is a kind of heat exchanger. The way of cooling or condensation is to exchange heat with the air outside the pipe through the pipe wall or fin. The air is generally provided by the fan, but the power consumption is large. And the cooling or condensation effect is susceptible to climate change.

1. Structure of air cooler

The air cooler is mainly composed of a tube bundle, a fan and a frame. The tube bundle includes a heat transfer tube, a tube box, a side beam, a beam, and the like. He can be arranged in three basic forms: horizontal, vertical and inclined. Among them, the horizontal arrangement heat transfer area is large, the air distribution is uniform, and the heat transfer effect is good; when the inclined roof is arranged, the fan is installed with the central space of the human characters, and the floor space is small and the structure is compact.

In order to counteract the effect of the lower heat transfer coefficient on the air side, a tube with fins on the outer wall of the light pipe is usually used. The finned tube acts as a heat transfer tube to expand the heat transfer area. The finned tubes are arranged in layers, and the two ends are connected to the tube box by welding or expansion. The tube is generally 3-8 rows. The tube bundle series is up to 12 meters in size. The outer diameter of the light pipe is usually 25 mm and 38 mm, the fin height is generally 12-15 mm, and the tube bundle width is 100-3000 mm. The finned tube is the core component of the air cooler, and its form and material directly affect the performance of the device. The pipe can be made of carbon steel, copper, aluminum and stainless steel; the fin material is determined according to the environment and manufacturing, and most of the industrial pure aluminum is used. In the case of high corrosion resistance or special remanufacturing conditions, copper or stainless steel.

The fins may be arranged in a lateral or longitudinal direction. The basic forms of finned tubes are: wound sheet, insert type, rolled sheet type, welded sheet type, elliptical tube type. The structure of the pipe box is mainly flange type, pipe block type and manifold type. Generally, the former is used for medium and low pressure, and the latter two are used for high pressure. In order to adapt to the thermal expansion of the tube bundle, the tube holder at one end is not fixed and is allowed to be displaced along the length of the tube.

2. Field of application of air cooler

Condensation of refinery, petrochemical overhead steam; cooling of reflux oil, bottom oil; cooling of various reaction products; cooling of circulating gas and condensation of steam turbine exhaust of power station.